Food Industry Technical
are leading specialists in intelligent energy saving ventilation control systems.

We have installed hundreds of systems for companies such as restaurants, hotels and supermarkets providing an outstanding return on investment.
Home
Products
Benefits
Energy Saving
Intelli-Hood Rental
Melink Europe
Our Service
News
White Papers
Case Studies
FAQ's
Links
About Us
Contact Us

Intelli-Hood typical system configuration

Intelli-Hood primarily controls the extract system to operate at the minimum level necessary, by monitoring the conditions in the zone and appropriately varying the speed of the extract fan.

Move your mouse pointer over the component parts below for more information.

The Extract SystemClick here to view our demo

Temperature Sensor

Exhaust air temperature is continuously monitored by sensors connected to the processor that varies the output of the drives controlling the extract fans-
Low output: when there is little or no cooking.
Increased output: when cooking activity increases, the heat sensors quickly detect this and the extract fan speed is increased to the appropriate level.
Temperature Sensor
Back to top

Air Purge Units

The Air Purge Units provide positive air pressure to the emitter and receiver housings and thereby significantly reduce the quantity of grease collecting on the lenses. Small fans are mounted above the extract canopies and connected to the emitter and receiver housings by pipe.
Air Purge Unit
Back to top

Variable Speed Drives

Extract fan speeds are controlled by Variable Frequency Drives (Inverters). The drives are housed in electronically conductive enclosures, fitted with appropriate filters and installed to ensure compliance with EMC regulations.
Variable Speed Drive
Back to top

System Processor

The processor monitors the inputs from the temperature and optics sensors communicating information to the variable speed drives controlling the extract fans. An I/O board serves a dual purpose: It primarily provides a 24Vdc power supply to the circuit board and air purge units and a 12Vdc supply to the optic sensors. It also provides a connection point for some of the inputs and outputs for the Autocal circuit board.
System Processor
Back to top

Keypad

Use the keypad to programme the system,find any faults or view the extract fan speeds for the programmed hoods.
"100%" Button - instant maximum fan speed for predetermined time, overriding the sensors.
Bar Graph - continuously displays the extract fan speeds on each hood being controlled and identifies a particular fault in the system.
Clean Light - flashes green/red if the optic sensors are faulty.
"SET UP" Button - scroll through the hood numbers and the programmable set-up options on the bar graph.
Keypad
Back to top

Optic Sensors

These consist of an infrared light beam emitter and receiver covering the length of the extract canopy. The receiver contains a photo detector which produces a variable low voltage signal depending on the amount of infrared light received. With the presence of smoke or steam, the light received will reduce and on detecting this the processor will signal the drive to ramp the fan motor to maximum speed.
Optic Sensor
Back to top